Part Number Hot Search : 
E004870 MIC52 HER101G APA3002 IPB180N MTRPB 74HC2 1SMC5372
Product Description
Full Text Search
 

To Download DH100ACDCLP Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 4-Wire Photoelectric, Low-Flow Duct Smoke Detector
System Sensor's Innovair DH100ACDCLP reduces the spread of smoke through HVAC air duct systems, including low-flow applications. As a photoelectric detector, it's ultra-responsive to the large smoke particles commonly found in duct systems.
The DH100ACDCLP uses low-flow technology to sense smoke in the lowest air speeds, from 100 to 4,000 feet per minute. When smoke is detected, all interconnected units will initiate their relays. However, to quickly locate the fire source, only the detector sensing smoke will alarm. Two DPDT Form-C relay contacts, connected to auxiliary equipment, can also be configured to prevent the spread of smoke through a particular area. The DH100ACDCLP is simple to install and maintain. Powered by 24 VAC/DC or 120/240 VAC, it can be easily mounted to round and rectangular ducts, from one to twelve feet in width, with outside mounting tabs. It also offers an adjustable telescopic sampling tube that can be used for duct widths up to 18 inches. This tube locks into place - no additional tools are necessary. Its modular construction allows for easy cleaning and field replacement of the power and sensor boards. Also simplifying maintenance is a transparent cover that provides convenient visual inspection. If the cover is removed, a patented cover-tamper trouble signal gives a 7-minute delay before the panel or remote accessory is notified of trouble. At a remote location, the remote test station option ensures that a detector is functioning properly and the remote sounder/LED indicator option signals if a detector is in alarm. However, the cover does not need to be removed if a detector needs to be reset at the detector. Simply push the built-in reset button. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors, NOT a substitute for early warning detection and NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information.
Features
* Photoelectric, low-flow technology * An air velocity rating from 100 feet per minute to 4,000 feet per minute (.5 meters per second to 20.32 meters per second) * Patented interconnectability for multi-fan shutdown * Two DPDT Form-C relay contacts * 24 VAC/DC or 120/240 VAC * Versatile mounting options * Outside mounting tabs * A patented telescopic sampling tube * Modular construction * A patented cover-tamper trouble signal * A transparent cover * A remote test station * Remote sounder/LED indicator options * A built-in reset button
Agency Listings
Innovair Duct Smoke Detector Specifications
Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100ACDCLP Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 m/sec.). The unit shall be capable of controlling up to ten (10) air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the SSK451 MultiSignaling Accessory or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or remote test station. The duct smoke detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be telescoping or be easily installed by passing through the duct housing after the housing is mounted to the duct. The unit shall provide a spacial separation of no less than 14 (6.4 mm) and/or a physical barrier between the high and low voltage terminals. The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size 1438 (37 cm.) Length; 51/2 (14 cm.) Width; 23/4 (7 cm.) Depth Shipping Weight 33/4 lbs. (1.7 kg.) Operating Temperature Range 32 to 131F (0 to 55C) Storage Temperature Range -22 to +158F (-30 to +70C) Operating Humidity Range 10% to 93% relative humidity non-condensing Air Duct Velocity 100 to 4000 ft./min. (0.5 to 20.32 m/sec.) Electrical Ratings - DH100ACDCLP (Includes Detector) Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 F max. 270 F max. N/A N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max. Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See detector label See detector label See detector label See detector label Current Requirements (Using No Accessories) Max. standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS* Max. alarm current 70 mA 125 mA RMS 35 mA RMS* 25 mA RMS* Contact Ratings Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor) Alarm auxiliary contacts (DPDT) 10A @ 30 VDC; 10A @ 250 VAC Note: Alarm auxiliary contacts must switch 100mA minimum at 5VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Trouble contacts (SPDT) 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm APA451 12.5 mA Max. n/a 30 mA Max. PA400 0 mA n/a 15 mA Max. RA400Z 0 mA n/a 10 mA Max. RTS451/RTS451KEY 12 mA* n/a 7.5 mA Max. SSK451 5 mA Max. 9 mA Max. 30 mA Max. *Note: When a unit is powered at the 120 VAC input, any combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state; 110 mA or less in the alarm state.
A05-1044-007
Wiring Guide
System wiring diagram for 4-wire duct smoke detectors
AVAILABLE POWER INPUTS POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. 9 10 A B C 9 AVAILABLE POWER INPUTS 10 A B C CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION.
24V
120 VAC
24V
120 VAC
220/240 VAC ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 18 7 17 6 C. N.O. N.O. C.
220/240 VAC ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 8 N.C. 16 N.C. 6 C. 17 N.O. 7 N.O. 18 C. 8 N.C. FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. NOTE: THE SUPERVISORY RELAY NOW PROVIDES A "FORM C" CONTACT FOR CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS, ONLY THE "NO" CONTACT IS USED
AUX. CONTACT RATINGS 10A @ 30 VDC RESISTIVE 10A @ 250 VAC 100mA MINIMUM @ 5 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS.
16 N.C.
ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. TROUBLE CONTACT RATING 2.0 A @ 30 VDC resistive 2.0 A @ 125 VAC resistive SUPERVISORY TROUBLE CONTACTS 14 3
ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS 14 3
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.
+
5 ALARM INITIATION LOOP ALARM INITIATION CONTACTS 4 CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. ALARM INITIATION CONTACTS 4 5 CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM.
-
UL LISTED 4-WIRE CONTROL PANEL FIRST DETECTOR IN THE LOOP DH100ACDCLP LAST DETECTOR IN THE LOOP DH100ACDCLP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
Wiring diagram for DH100ACDCLP to APA451:
DH100ACDCLP Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power - 15 19 14 3 20 3 Power (Green LED) 1 Common APA451 2 Alarm (Red LED)
Wiring diagram for the DH100ACDCLP to RTS451/RTS451KEY:
DH100ACDCLP Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power - Reset 15 19 14 3 20 2 6 RTS451/RTS451KEY 1 (Red LED) Alarm
Wiring diagrams for optional accessories:
15 ALARM SIGNAL (+) AUX POWER (-) 20
(+) ALARM SIGNAL (+) AUX POWER (-) (-)
15
*For RTS451KEY only without a
control panel. (Green LED) Power
*
20
DUCT DETECTOR DH100ACDCLP
PA400 (OPTIONAL) AUDIBLE ALERT
DUCT DETECTOR DH100ACDCLP
2 3
NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
15
Test 11 SIGNAL (+) ALARM
4 5
(+) ALARM SIGNAL (+) AUX POWER (-)
15
(+)
Wiring diagram for DH100ACDCLP to SSK451:
FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SSK451 COMMON TEMPORAL SELECT ALARM SIGNAL SUPERVISORY SIGNAL RESET TEST POWER (-) POWER (+) 3 2 1 4 7 8 6 5 15 3 14 2 11 20 19 ALARM SIGNAL NO SUPERVISORY CONTACT DH100ACDCLP
RESET TEST AUX. POWER (-) AUX. POWER (+)
*NOTE: For RTS451KEY only without a Control 20 (-) Panel. RTS451 doesDUCT DETECTOR not have a terminal 6. PA400 (OPTIONAL) DH100ACDCLP AUDIBLE ALERT NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
AUX POWER (-)
RED 20 (-)
DUCT DETECTOR DH100ACDCLP
RA400Z (OPTIONAL) REMOTE (LED) ANNUNCIATOR
FIELD INSTALLED JUMPER
Important Interconnect Notes
* When using the interconnect feature, all interconnected units must be powered with the same, independent supply. * Polarity must be maintained throughout the interconnect wiring. Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 and so on. * Up to 10 units may be interconnected.
A05-1044-007
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations, and several different means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed.
APA451 Piezo Annunciator (UL S4011)
RTS451KEY Remote Test Station with Key (UL S2522)
PA400W Mini-Alert Sounder (UL S3593) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available)
RTS451 Remote Test Station (UL S2522)
RA400Z Remote Annunciator (UL S2522)
SSK451 Multi-Signaling Accessory (UL 268A)
SSK451 Multi-Signaling Accessory (UL 268A) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available)
Ordering Information
Part No. DH100ACDCLP A5190 A5064 Accessories ST-1.5 ST-3 ST-5 ST-10 T80-71-00 P48-55-00 SSK451 RTS451KEY RTS451 APA451 Description 4-wire photoelectric duct detector with low-flow technology Replacement 4-wire photoelectric detector board Replacement 4-wire power board Metal sampling tube duct widths 1-2 (0.3-0.6 m) Metal sampling tube duct widths 2-4 (0.6-1.2 m) Metal sampling tube duct widths 4-8 (1.2-2.4 m) Metal sampling tube duct widths 8-12 (2.4-3.7 m) Replacement telescoping sampling tube Replacement end cap for T80-71-00 Multi-Signaling accessory Remote test station with key lock Remote test station Remote annunciator with piezo alarm MOD400R RA400Z F36-09-11 M02-04-00 P48-21-00 S08-39-01 PA400W PS24LOW PS12/24SLENSW PS12/24SLENSC Sensitivity test module Remote annunciator alarm LED Replacement air filters (two per package) Test magnet End cap for metal sampling tubes Photo replacement screen Mini-Alert sounder Mini-Alert add-on strobe Wall-mount "SMOKE" lens Ceiling-mount "SMOKE" lens
3825 Ohio Avenue * St. Charles, IL 60174 Phone: 800-SENSOR2 * Fax: 630-377-6495
(c)2006 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-1044-007 * 7/06 * #1676


▲Up To Search▲   

 
Price & Availability of DH100ACDCLP

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X